IEK
ARMAT AR-A5V TD40 3P W VR Air Circuit Breaker 125kA trip unit TD 4000A 3P withdrawable with accessories ~220-240V: shunt trip, closing release, motor drive IEK AR-ACB-3VG-125-4000A-TDCF
SKU: AR-ACB-3VG-125-4000A-TDCF
ETIM: EC000228
5,054,608 ₽
Get back 50,546 ₽ in points
Analogues by specifications
Stock by warehouse
Please note - in order to improve Customer convenience, we are transitioning from horizontal to vertical busbar connection for frame sizes G and H in the basic configuration. In ACB ARMAT data for frame sizes manufactured from February 2025 (batch 2502), vertical connection is used. Since we have single units of ACB ARMAT frame sizes G and H oriented for horizontal connection in stock - please consult with us before placing an order. ARMAT series Air Circuit Breakers (ACB) are designed to protect power supply networks from short circuits and overloads, as well as for the rapid switching of electrical circuit sections, and are designed for use in electrical installations with a rated operating voltage of up to 690 V and rated currents from 630 to 6300A. These circuit breakers are equipped with electronic trip units with various combinations of functional features, including Modbus communication capability, which, given a breaking capacity of up to 150 kA, allows the use of ACB ARMAT in any type of industrial and civil facilities. Compliant with GOST R 50030.2.
Main circuit connection type
Rear connection
Built-in motor drive
Yes
Height
435.0 мм
Height
435.0 мм
Altitude above sea level
< 2000
Depth
390.0 мм
Overload protection device setting range to
4000 А
Setting range of overload protection device from
1600...4000 А
Instantaneous short-circuit release setting range to
80000 А
Instantaneous short-circuit release setting range from
4000...80000 А
Auxiliary device factory-installed
Shunt release (for power circuit breakers)
Design
Withdrawable
Number of auxiliary NO contacts
0
Number of auxiliary changeover contacts
6
Number of auxiliary break contacts
0
Number of poles
3
Design
Other
Mechanical endurance without maintenance
12500
Motor drive optional
No
Electronic release available
Yes
Rated impulse withstand voltage
12
Rated short-time withstand current Icw for 1 s
125
Rated service short-circuit breaking capacity Ics
125
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
125 кА
Rated insulation voltage Ui
1250 В
Rated voltage up to
690 В
Rated voltage from
690...690 В
Rated current
4000 А
Rated continuous current Iu
4000 А
Suitable for DIN-rail mounting
No
Power loss
1100 Вт
Operating mode
Continuous
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP30
Product/component type
Air circuit breaker
Main electrical circuit connection type
Bolted connection
Control element type
Other
Mains supply frequency
50 Гц
Width
580.0 мм
Electrical endurance without maintenance at AC 690V
2000
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
637952 ₽
CHINT Air circuit breaker 3p 800A 55kA AC400V type H NA8-1600N-800H/3P drawout (R) CHINT 410992
SKU: 410992
970862 ₽
CHINT Air circuit breaker 4p 1250A 66kA NA8-1600H-1250S/4P AC 400V type S stac. (R) CHINT 530576
SKU: 530576
1442554 ₽
CHINT Air circuit breaker NA8-4000H-2000H/3P stac. 2000A 100kA type H AC230V (R) CHINT 262721
SKU: 262721
816092 ₽
CHINT Air circuit breaker 3p 1000A 85kA NA8-2500H-1000M AC 230V type M CHINT 262426
SKU: 262426