Контактор (группа IEK)
Automatic circuit breaker AB2M20H-53-43-2000-MP4-12500-UHL3-NR220VDC-PE220VDC-3p3w 2000A elect.mag. release 12500A; max. current release MRT4-MP; shunt release 220VDC; elect.mag. actuator 220VDC; free contacts 3p3w Contactor 1024641
SKU: 1024641
ETIM: EC000228
913,294 ₽
Get back 9,132 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Front connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Depth
320.0 мм
Short-time delayed short-circuit release range
720…24000 А
Overload protection device setting range to
1980 А
Setting range of overload protection device from
600…2000 А
Instantaneous short-circuit release setting range to
32000 А
Instantaneous short-circuit release setting range from
8000 А
Version
Stationary
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Built-in device for built-in appliances
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
2000 А
Rated continuous current Iu
2000 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Main electrical circuit connection type
Bolted connection
Control element type
Other
Mains supply frequency
50/60 Гц
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
320605 ₽
CHINT Molded case circuit breaker 3p 1250A 100kA NM8N-1600H EN with elec. release (R) CHINT 263124
SKU: 263124
131065 ₽
CHINT Molded Case Circuit Breaker 4p 63A 70kA NM8N-250Q EM with electronic trip unit LCD (R) CHINT 271397
SKU: 271397
483673 ₽
CHINT Air circuit breaker 3p 1250A 66kA NA8-1600H-1250M/3P AC 400V type M stac. (R) CHINT 536990
SKU: 536990
38644 ₽
CHINT Molded case circuit breaker 4p 125A 150kA NM8N-125R TM with reg. thermomagnetic release (R) CHINT 271730
SKU: 271730