Контактор (группа IEK)
Circuit breaker AV2M4SV-55-41-400-MP4-UKHL3-NR220VAC-PE220VAC-3p3w 400A; max. trip current el. trip. MRT4-MP; shunt trip 220VAC; electromagnetic drive 220VAC; free contacts 3p3w Contactor 1000555
SKU: 1000555
ETIM: EC000228
622,425 ₽
Get back 6,224 ₽ in points
Promo code
FIRST
— cashback ×3 on your first order: 3% in points on the first 50,000 ₽
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Rear connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Height
500.0 мм
Short-time delayed short-circuit release range
144…5280 А
Overload protection device setting range to
440 А
Setting range of overload protection device from
120…440 А
Instantaneous short-circuit release setting range to
6400 А
Instantaneous short-circuit release setting range from
1600 А
Version
Withdrawable
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Slot-in device (withdrawable)
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
400 А
Rated continuous current Iu
400 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Control element type
Other
Mains supply frequency
50/60 Гц
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
3062 ₽
Generica (Группа IEK) Circuit breaker VA66-31 3P 40A 18kA GENERICA SAV10-3-0040-G
SKU: SAV10-3-0040-G
2652 ₽
КЭАЗ Circuit breaker 1p 4A 10kA 1.8kA A63 МГ У3 400V AC КЭАЗ 104125
SKU: 104125
3951 ₽
КЭАЗ Circuit breaker 2p 2.5A 10In 0.4kA AP50B 2M U3 400V AC/220V DC KEAZ 106458
SKU: 106458
1911 ₽
EKF Circuit Breaker VA-99ML 63/ 32A 3P 15kA EKF Basic mccb99-63-32mi
SKU: mccb99-63-32mi