6,709 ₽
Get back 67 ₽ in points
Analogues by specifications
Stock by warehouse
• Designed for connecting 4-core cables:
• with paper oil-impregnated or plastic insulation
• with or without armor
• with a common aluminum or lead sheath
• for voltage up to 1 kV
• Complies with GOST 34839-2022 requirements
• Types of cables to be mounted: AABl, (A)SBl, (A)SKl, (A)SBG, AAG, (A)SG, AABv, (A)SBShv, AASHv, (A)AShv, AAB2lShv, (A)SB2lShv
• Insulating sleeve cuffs ensure reliable and high-quality insulation of the cable core connection points
• Thermoplastic adhesive applied to the inner surface of the connection sleeves, gloves, and the sheath ensures complete tightness of the sleeve after installation
• Installation of the jumper wire connecting the sheaths and armor tape at both ends of the cable is carried out by a combined method. The standard kit includes constant pressure springs used for fastening the ground wire to the metal sheaths. Fastening to the armor tape is carried out by soldering
• When installing the grounding unit on a cable with armor made of steel or aluminum wires, it is necessary to additionally use the "KMPB grounding kit" corresponding to the selected sleeve
• The presence of constant pressure springs for fastening the ground wire to the metal sheaths of the connected cables ensures fast and reliable installation. The use of a spring eliminates the possible risk of thermal damage to the paper insulation under the aluminum sheath in case of soldering using high-melting-point solder "A"
• The sleeve kit is universal and allows the use of both crimp connectors and bolted connectors
• High quality of components and composite materials used
• Installation tools: PG (KVT) propane burner, NMB-6 (KVT) bolt head and connector removal kit
• All polymer compositions used for the production of KVT heat-shrinkable components are halogen-free (HF=Halogen Free)
• Manufactured according to TU 3599-006-97284872-2006
For connecting cables with paper and plastic insulation
Yes
Approval for mining industry use
No
Design
Heat-shrink
Number of cores
4
Halogen-free
Yes
Rated voltage U0/U (Um)
0.6/1 (1.2) kV
Rated conductor cross-section at
50 кв.мм
Rated conductor cross-section from
25 кв.мм
With concentric screening
No
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
552 ₽
КВТ Cable Joint Kit 3PST(b) mini-1/2.5 ng-LS 74677 KVT
SKU: 74677
14867 ₽
Подольский ЗЭМИ 10kV Cable connection sleeve Stp-10-25/50-03-3 with non-soldered grounding node 9036593 Podolsk stpx10x025x50x03z Podolsky ZEMI
SKU: stpx10x025x50x03z
19416 ₽
Подольский ЗЭМИ Cable connection sleeve 20kV 1PSt20-300-V with sleeves 9014940 Podolsk 1pst20x300v Podolsky ZEMI
SKU: 1pst20x300v
5650 ₽
КВТ Cable branch joint 4PTO-1-16/50-1.5/6 66584 KVT
SKU: 66584