Контактор (группа IEK)
Automatic circuit breaker AB2M20NV-53-43-1500-MR4-12500-O4-PE220VDC-3p4z 1500A electr.mag. trip 12500A; max. current trip MRT4-MP; electr.mag. drive 220VDC; free contacts 3p4z Contactor 1037065
SKU: 1037065
ETIM: EC000228
1,664,682 ₽
Get back 16,646 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Rear connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Short-time delayed short-circuit release range
540…18000 А
Overload protection device setting range to
1650 А
Setting range of overload protection device from
450…1500 А
Design
Withdrawable
Climatic version
UKhL3
Number of auxiliary NO contacts
4
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Slot-in device (withdrawable)
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
1500 А
Rated continuous current Iu
1500 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Control element type
Other
Mains supply frequency
50/60 Гц
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
66558 ₽
CHINT Circuit breaker 3p 400A 70kA NXMS-400H with elec. release (R) CHINT 845726
SKU: 845726
1332441 ₽
CHINT Air circuit breaker NA8-2500H-1600H/3P withdrawable 1600A 85kA type H AC230V (R) CHINT 262495
SKU: 262495
31699 ₽
CHINT Circuit breaker 4p 16A 36kA NM8NDC-125C TM with reg. thermomagnetic release (R) CHINT 271791
SKU: 271791
22013 ₽
CHINT Circuit breaker 2p 32A 36kA NM8NDC-125C TM with reg. thermomagnetic trip (R) CHINT 275588
SKU: 275588