Контактор (группа IEK)
Circuit breaker AV2M20SV-55-43-1500-MP4-UHL3-NR230VAC-PE220VAC-3p3z-VKS 1500A; max current trip unit MRT4-MP; independent trip coil 220VAC; electromagnetic drive 220VAC; free contacts 3p3z without control box Contactor 1042823
SKU: 1042823
ETIM: EC000228
1,472,600 ₽
Get back 14,726 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Rear connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Short-time delayed short-circuit release range
540…18000 А
Setting range of overload protection device from
450…1500 А
Design
Withdrawable
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Slot-in device (withdrawable)
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
1500 А
Rated continuous current Iu
1500 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Control element type
Other
Mains supply frequency
50/60 Гц
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
196710 ₽
CHINT 4P 630A 25kA NM8NDC-800B TM automatic circuit breaker with reg. thermomagnetic trip (R) CHINT 272995
SKU: 272995
637952 ₽