Контактор (группа IEK)
Circuit breaker 3p 250A AV2M4NV-53-41 UHL3 690V Contactor 1035455 Contactor (IEK group)
SKU: 1035455
ETIM: EC000228
734,116 ₽
Get back 7,341 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Rear connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Height
500.0 мм
Short-time delayed short-circuit release range
90…3300 А
Overload protection device setting range to
275 А
Setting range of overload protection device from
75…275 А
Design
Withdrawable
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Slot-in device (withdrawable)
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
250 А
Rated continuous current Iu
250 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Control element type
Other
Mains supply frequency
50/60 Гц
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
1311412 ₽
CHINT Air circuit breaker NA8-4000H-1600H/3P stationary 1600A 100kA type H AC400V (R) CHINT 262733
SKU: 262733
119290 ₽
CHINT Circuit breaker 3p 315A 70kA NM8NDC-630Q TM with reg. thermomagnetic release (R) CHINT 269364
SKU: 269364
137185 ₽
CHINT Circuit breaker 4p 350A 150kA NM8N-630R TM with reg. thermomagnetic release (R) CHINT 269305
SKU: 269305
104472 ₽
CHINT Circuit breaker 3p 250A 70kA NM8N-400Q EN with elec. trip (R) CHINT 269406
SKU: 269406