Контактор (группа IEK)
Circuit breaker AV2M4S-55-41-250-MP4-UKHL3-HP220VDC-PE220VDC-3r3pz 250A; max trip current elec. trip. MRT4-MP; shunt trip 220VDC; electromagnetic drive 220VDC; free contacts 3r3pz Contactor 1015626
SKU: 1015626
ETIM: EC000228
536,511 ₽
Get back 5,365 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Front connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Depth
297.0 мм
Short-time delayed short-circuit release range
90…3300 А
Overload protection device setting range to
275 А
Setting range of overload protection device from
75…275 А
Instantaneous short-circuit release setting range to
4000 А
Instantaneous short-circuit release setting range from
1000 А
Design
Stationary
Version
Stationary
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Built-in device for built-in appliances
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
250 А
Rated continuous current Iu
250 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Main electrical circuit connection type
Bolted connection
Control element type
Other
Mains supply frequency
50/60 Гц
Width
405.0 мм
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
580406 ₽
CHINT Air circuit breaker 4p 1250A 66kA NA8-1600H-1250M/4P AC 230V type M stac. (R) CHINT 537257
SKU: 537257
3686492 ₽
CHINT Air circuit breaker 4p 4000A 75kA NA8-4000HU-4000S/4P AC 230V type S withdrawable (R) CHINT 530706
SKU: 530706
Price on request
CHINT Circuit breaker 3p 800A 50kA NM8N-800S EN with elec. release (R) CHINT 273034
SKU: 273034
49710 ₽
CHINT Motor protection circuit breaker 3p 160A 50kA NM8N-250S ENM (R) CHINT 271459
SKU: 271459