Контактор (группа IEK)
Circuit breaker AB2M4S-55-41-400-MP4-UHL3-HP380VAC-PE220VAC-3p3w 400A; max. trip current MR T4-MP; undervoltage release 380VAC; electromagnetic drive 220VAC; free contacts 3p3w Contactor 1020657
SKU: 1020657
ETIM: EC000228
536,511 ₽
Get back 5,365 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Front connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Depth
297.0 мм
Short-time delayed short-circuit release range
144…5280 А
Overload protection device setting range to
440 А
Setting range of overload protection device from
120…440 А
Design
Stationary
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Built-in device for built-in appliances
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
400 А
Rated continuous current Iu
400 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Main electrical circuit connection type
Bolted connection
Control element type
Other
Mains supply frequency
50/60 Гц
Width
405.0 мм
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
1286652 ₽
CHINT Air Circuit Breaker NA8-2500HU-800M/4P stationary 800A 65kA type M AC 230V (R) CHINT 406184
SKU: 406184
59652 ₽
CHINT Motor protection circuit breaker 3p 250A 50kA NM8N-250S EMM LCD (R) CHINT 271485
SKU: 271485
638272 ₽
CHINT Air circuit breaker 3p 630A 66kA NA8-1600H-630H/3P AC 400V type H withdrawable (R) CHINT 537240
SKU: 537240
157507 ₽
CHINT Circuit breaker 3p 32A 150kA NM8N-250R EM with LCD (R) electric release CHINT 271411
SKU: 271411