Контактор (группа IEK)
Automatic circuit breaker АВ2М4С-55-41-400-МР4-УХЛ3-НР380ВAC-ПЭ220ВDC-3p3z 400A; max current trip unit МРТ4-МП; independent trip coil 380V AC; electromagnetic drive 220V DC; free contacts 3p3z Contactor 1037818
SKU: 1037818
ETIM: EC000228
536,511 ₽
Get back 5,365 ₽ in points
Analogues by specifications
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
Main circuit connection type
Front connection
Built-in ground fault protection
No
Built-in motor drive
Yes
Depth
297.0 мм
Short-time delayed short-circuit release range
144…5280 А
Overload protection device setting range to
440 А
Setting range of overload protection device from
120…440 А
Design
Stationary
Climatic version
UKhL3
Number of auxiliary NO contacts
3
Number of auxiliary changeover contacts
0
Number of auxiliary break contacts
3
Number of poles
3
Design
Built-in device for built-in appliances
Motor drive optional
Yes
Electronic release available
Yes
Rated impulse withstand voltage
6
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz
23 кА
Rated voltage
690 В
Rated voltage from
0...690 В
Rated current
400 А
Rated continuous current Iu
400 А
Suitable for DIN-rail mounting
No
Power loss
348 Вт
With minimum voltage protection
Yes
Tripping system
Electronic
IP protection rating
IP00
Product/component type
Moulded case circuit breaker
Main electrical circuit connection type
Bolted connection
Control element type
Other
Mains supply frequency
50/60 Гц
Width
405.0 мм
0
★★★★★
0 reviews
No reviews yet. Be the first!
Leave a review
Related products
22013 ₽
CHINT Circuit breaker NM8NDC-250C TM 1p 125A 36kA with reg. thermomagnetic release (R) CHINT 330527
SKU: 330527
40601 ₽
CHINT Circuit breaker 4p 225A 50kA NM8N-250S TM with reg. thermomagnetic release (R) CHINT 271187
SKU: 271187
1334709 ₽
CHINT Air circuit breaker NA8-4000H-3200M/3P drawout 3200A 100kA type M DC220V (R) CHINT 262711
SKU: 262711
1030852 ₽
CHINT Air circuit breaker NA8-2500H-1250M/4P drawout 1250A 85kA type M DC220V (R) CHINT 262597
SKU: 262597