Контактор (группа IEK)
Automatic circuit breaker AB2M20HB-53-43-1500-MP4-12500-UKHL3-HP220VDC-PE220VAC-3p3w 1500A electr. mag. release 12500A; max. current release MRT4-MP; independent release 220VDC; electr. mag. drive 220VAC; free contacts 3p3w Contactor 1028808
SKU: 1028808
ETIM: EC000228
1024418 ₽
Price list (incl. VAT):
1096128 ₽
Preorder
Switches are intended to replace the AVM series circuit breakers in operation and are manufactured based on the VA50-41 and VA50-43 series switches. The switches are used in AC electrical circuits with a rated voltage of up to 660 V at a frequency of 50 or 60 Hz for conducting current in normal mode and disconnecting during short circuits and overloads, as well as for infrequent (up to 10 times per day) operational switching of these circuits. The series is included in the list of domestic products according to RF Decree No. 719 (Ministry of Industry and Trade register).
AV2M4N-53-41 – non-selective for rated currents 250 and 400 A
AV2M4S-55-41 – selective for rated currents 250 and 400 A
AV2M10N-53-41 – non-selective for rated currents 800 and 1000 A
AV2M10S-55-41 – selective for rated currents 800 and 1000 A
AV2M15N-53-43 – non-selective for rated currents 1200 and 1500 A.
AV2M15S-55-43 – selective for rated currents 1200 and 1500 A.
AV2M20N-53-43 – non-selective for rated currents 1500 and 2000 A.
AV2M20S-55-43 – selective for rated currents 1500 and 2000 A.
AV2M4-56-41 – without maximum current trips for rated current 400 A.
AV2M10-56-41 - without maximum current trips for rated currents 800 and 1000 A.
AV2M15-56-43 – without maximum current trips for rated currents 1200 and 1500 A.
AV2M20-56-43 - without maximum current trips for rated currents 1500 and 2000 A.
| Main circuit connection type | Rear connection |
| Built-in ground fault protection | No |
| Built-in motor drive | Yes |
| Short-time delayed short-circuit release range | 540…18000 А |
| Overload protection device setting range to | 1650 А |
| Setting range of overload protection device from | 450…1500 А |
| Instantaneous short-circuit release setting range to | 24000 А |
| Instantaneous short-circuit release setting range from | 6000 А |
| Version | Withdrawable |
| Climatic version | UKhL3 |
| Number of auxiliary NO contacts | 3 |
| Number of auxiliary changeover contacts | 0 |
| Number of auxiliary break contacts | 3 |
| Number of poles | 3 |
| Design | Slot-in device (withdrawable) |
| Motor drive optional | Yes |
| Electronic release available | Yes |
| Rated impulse withstand voltage | 6 |
| Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz | 23 кА |
| Rated voltage | 690 В |
| Rated voltage from | 0...690 В |
| Rated current | 1500 А |
| Rated continuous current Iu | 1500 А |
| Suitable for DIN-rail mounting | No |
| Power loss | 348 Вт |
| With minimum voltage protection | Yes |
| Tripping system | Electronic |
| IP protection rating | IP00 |
| Product/component type | Moulded case circuit breaker |
| Control element type | Other |
| Mains supply frequency | 50/60 Гц |
0
★★★★★
0 reviews
No reviews yet. Be the first!