ZVZ 481M clamp is designed for voltage measurement, short-circuiting, or protective grounding of a line using short-circuiting devices such as UZK-5, UZK-6, UZK-7, M5D, M6D, M7D, grounding devices of the UZM type, or universal short-circuiting and grounding devices UZMK-5, UZMK-6, UZMK-7 when performing work on overhead lines.
It is installed on the conductive and neutral cores of SIP for the entire service life of the line (usually at its beginning and end). To access the bronze plug contact with a lock, the insulating cap is removed. The plug contact has a hole for checking the absence of voltage.
The ability to fix the lower part of the clamp with an S17 key facilitates bolt tightening.
Manufactured according to TU 3449-004-52819896-2010.
Maximum conductor cross-section
150 кв.мм
Rated conductor cross-section
16 кв.мм
System type
SIP-2/SIP-4