Sistemnye Resheniya

Electrical equipment for a construction site: what the codes require

Requirements for the temporary power supply of a construction site: distribution panels, protective devices and earthing per the PUE and SNiP codes.

Contents
Electrical equipment for a construction site: what the codes require

Regulatory framework

The temporary power supply of construction sites is governed by:

  • PUE, 7th edition (Chapter 7.1 – electrical installations of buildings; Chapter 6.1 – electric lighting)
  • SNiP 12-03-2001 "Occupational safety in construction"
  • GOST R 50571.7.704-2013 (requirements for electrical installations on construction sites)
  • SP 48.13330.2019 "Organization of construction"

Power supply intake

The temporary connection is arranged through the power supply utility. At the intake point an input distribution unit (VRU) is installed, equipped with:

  • An input switch-disconnector or circuit breaker
  • An electricity meter
  • A residual current device (RCD) at the intake

Distribution panels

Two types of panels are used on a construction site:

VRU (input distribution unit) – the site's main panel. Degree of protection no lower than IP44.

Distribution boards (RP) – intermediate boards for connecting a group of loads. Installed in the work area.

All panels must be fitted with:

  • Circuit breakers on each outgoing line
  • RCDs with a 30 mA leakage current on all socket groups (PUE clauses 7.1.79, 7.1.82)
  • CEE-type industrial sockets with degree of protection IP44
  • A voltage-presence indicator

Mandatory protective devices

  • Circuit breakers – on each line, characteristic C or D
  • 30 mA RCD – mandatory for all socket groups and portable tools
  • 10 mA RCD – for especially hazardous conditions (damp premises, work in excavation pits)
  • Circuit breaker at the intake – for overall protection and the ability to shut everything off completely

Earthing

A TN-S or TN-C-S earthing system is mandatory on a construction site. Requirements:

  • Repeated earthing of the PEN conductor at the intake – no more than 30 Ω (PUE clause 1.7.103); 4 Ω applies to the earthing arrangement of the source neutral (clause 1.7.101)
  • All metal equipment enclosures earthed
  • Scaffolding and fencing connected to the earthing loop
  • Equipotential bonding conductors – at least 6 mm² in copper or 16 mm² in aluminium; the cross-section of the PE protective conductor is selected per PUE table 1.7.5

Cable runs

  • For fixed runs: VVGng-LS cable in protective conduits or trays
  • For temporary connections: KG cable (flexible) with rubber insulation
  • Outdoor temporary wiring on supports: no lower than 2.5 m above workplaces, 3.5 m above walkways and 6 m above driveways
  • Across driveways: in conduits buried to 0.8 m, or on supports at a height of at least 6 m

Portable electrical equipment

  • Class II power tools (double insulation) or Class III (42 V) for damp premises
  • Extension cords – KG cable 3×1.5 mm² or 3×2.5 mm². For extension cords on cable reels the limiting length is set by GOST 31223-2012: 60 m for a 1.5 mm² cross-section. The length is verified by a voltage-drop calculation: 1.5 mm² at a current of 16 A over 60 m gives about 10% loss
  • Portable luminaires – voltage no higher than 50 V (PUE clause 6.1.17)

Minimum kit for a construction site

  1. IP54 input panel with a meter, switch-disconnector and RCD
  2. 1–2 IP44 distribution boards with circuit breakers and 30 mA RCDs
  3. VVGng-LS or KG cable for wiring
  4. Earthing kit (rods, strip, clamps)
  5. CEE IP44 sockets for connecting equipment

All the electrical equipment you need for a construction site is in our catalogue. We will advise you on selecting a kit.

View in catalog: Construction Site Distribution Board, Complete Switchboard Equipment, Modular Circuit Breaker (MCB), Cables and Wires for Flexible (Non-Fixed) Installation.

Need help choosing?

Our engineers will help select equipment for your project.

Send diagram +7 (4812) 54-82-55